GE 165 FSX

Generator Diesel FPT (IVECO) NEF67 TE1F - Three-phase synchronous alternator - Water Cooled

POWER RATINGS

  • Stand-By three-phase power: 168 kVA (134.4 kW) /400V / 242.5 A
  • PRP three-phase power: 153 kVA (122.4 kW) / 400V / 221 A
  • COP three-phase power: 122 kVA (97.6 kW) / 400V / 176.3 A
  • Frequency: 50 Hz
GENERAL SPECIFICATIONS

  • Fuel tank capacity: 425 lt.
  • Running time (75% to PRP): 16 h
  • Measured acoustic power LwA (pressure LpA): 93 dB(A) (68 dB(A) @ 7m)
  • Guaranteed acoustic power LwA (pressure LpA): 94 dB(A) (69 dB(A) @ 7m)
  • Dry Weight: 2700 kg
  • Dimensions (LxWxH): 3750x1400x2030 mm

More Information

Engine

Model Fuel Starter Output Stand By Output PRP Cylinders / Displacement Speed Cooled
FPT (IVECO) NEF67 TE1F Diesel Eletric 145 kW (197.2 HP) 131.5 kW (178.8 HP) 6/ 6700 cm3 1500 rpm Water

OPTIONS ON REQUEST