GE 165 FXC

Generator Diesel FPT (IVECO) NEF67 TE1F - Three-phase synchronous alternator - Water Cooled

POWER RATINGS

  • Stand-By three-phase power: 165 kVA (132 kW) / 400V / 238,2A
  • PRP three-phase power: 150 kVA (120 kW) / 400V / 216,5 A
  • COP three-phase power: 122 kVA (97.6 kW) / 400V / 176.3 A
  • Frequency: 50 Hz
GENERAL SPECIFICATIONS

  • Fuel tank capacity: 230 lt.
  • Running time (75% to PRP): 9 h
  • Measured acoustic power LwA (pressure LpA): 94.6 dB(A) (69.6 dB(A) @ 7m)
  • Guaranteed acoustic power LwA (pressure LpA): 96 dB(A) (71 dB(A) @ 7m)
  • Dry Weight: 2160 kg
  • Dimensions (LxWxH): 3400x1200x1800 mm

More Information

Engine

Model Fuel Starter Output Stand By Output PRP Cylinders / Displacement Speed Cooled
FPT (IVECO) NEF67 TE1F Diesel Eletric 145 kW (197.2 HP) 131.5 kW (178.8 HP) 6/ 6700 cm3 1500 rpm Water

OPTIONS ON REQUEST