GE 45 KSX

Diesel generating set KOHLER - KDI 2504TM-40 - Three-phase synchronous alternator  - Water Cooled

POWER RATINGS THREE-PHASE

  • Stand-By three-phase power: 44 kVA(35.2 kW) / 400V /63.5A
  • PRP three-phase power: 40 kVA(32 kW) / 400V / 57.7A
  • PRP single-phase power: 15.5 kVA / kW /230V / 67.4A
  • Frequency: 50 Hz
GENERAL SPECIFICATIONS

  • Fuel tank capacity: 100 lt.
  • Running time (75% to PRP): 14 h
  • Measured acoustic power LwA (pressure LpA): 91 dB(A) (66 dB(A) @ 7m)
  • Guaranteed acoustic power LwA (pressure LpA): 93 dB(A) (68 dB(A) @ 7m)
  • Dry Weight: 1033 Kg
  • Dimensions (LxWxH): 2050x900x1428 mm

More Information

Engine

Model Fuel Starter Output Stand By Output PRP Cylinders / Displacement Speed Cooled
KOHLER - KDI 2504TM-40 Diesel Electric 39.9 kW (54.3 hp) 36.2 kW (49.2 hp) 4 / 2482 cm³ (2.482 lt.) 1500 rpm Water

AVR

sample powersafe The Automatic Vcoltage Regulator (AVR) is an electronic device that regulates the voltage level at all times to maintain precise AC output from the generating set. The AVR calculates how much voltage has to be sent to the exciter numerous times a second, therefore stabilising the output voltage to a predetermined set point.

The control characteristics of an AVR system are much more accurate than those of self-regulated alternators.

OPTIONS ON REQUEST

Other models that may interest you