GE 455 FSX

Generator Diesel FPT (IVECO)  C13 TE3A - Three-phase synchronous alternator - Water Cooled

POWER RATINGS

  • Stand-By three-phase power: 450 kVA (360 kW)/ 400V / 649.5A
  • PRP three-phase power: 410 kVA (328 kW)/ 400V / 592A
  • COP three-phase power: 315 kVA (252 kW) / 400V / 455.2 A
  • Frequency: 50 Hz
GENERAL SPECIFICATIONS
  • Fuel tank capacity: 580 lt.
  • Running time (75% to PRP): 8.5 h
  • Acoustic pressure: 72 dB(A) @ 7m
  • Dry Weight: 4240 kg
  • Dimensions (LxWxH): 4100x1520x2150 mm

More Information

Engine

Model Fuel Starter Output Stand By Output PRP Cylinders / Displacement Speed Cooled
FPT (IVECO) C13 TE2F Diesel Eletric 377 kW (512.7 HP) 342 kW (465.1 HP) 6/ 12900 cm³ 1500 rpm Water
FPT (IVECO) C13 TE3A Diesel Electric 387 kW (526.3 HP) 352 kW (478.7 HP) 6/ 12900 cm³ 1500 rpm Water

Technical Features

INFO
  • Engine protection EP6
  • Automatic voltage regulator “AVR
  • Common-rail engines with electronic governor
  • Closed crankcase ventilation
  • Four pole circuit breaker
  • Oil drain pump
  • Bunded base  with drain plug
  • Two central lifting eyes
  • Ready for connection to automatic transfer unit EAS

GENERAL
  • IP protection degree: 44
  • Dimension:  4100x1520x2150 mm
  • Dry weight : 4240 kg (FPT (IVECO) C13 TE3A)
  • Dry weight : 4100 kg (FPT (IVECO) C13 TE2F)
  • Measured acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7m)
  • Guaranteed acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7m)

AVR

sample powersafe The Automatic Vcoltage Regulator (AVR) is an electronic device that regulates the voltage level at all times to maintain precise AC output from the generating set. The AVR calculates how much voltage has to be sent to the exciter numerous times a second, therefore stabilising the output voltage to a predetermined set point.

The control characteristics of an AVR system are much more accurate than those of self-regulated alternators.

OPTIONS ON REQUEST